RECOMMENDED LIMITS FOR MINERAL INSULATING OILS AFTER INITIAL FILLING OF ELECTRIC
EQUIPMENT, BEFORE ENERGIZING- |
|||
Test |
Limits |
||
Voltage(HV), kV |
|||
<72.5 |
72.5 to 170 |
>170 |
|
Breakdown Voltage (kV/cm) |
>220 |
>260 |
>260 |
Water Content (mg/g) |
<20 |
<10 |
<10 |
Neutralisation Number (mgKOH/g) |
<0.03 |
<0.03 |
<0.03 |
Interfacial Tension (mN/m) |
>35 |
>35 |
>35 |
Dielectric Dissipation Factor - |
<0.015 |
<0.015 |
<0.010 |
Oxidation Stability |
Acc. to IEC60296 (for unused oils) |
||
Particles (ISO4406) |
/ |
/ |
9/6 to 10/7 |