Specification |
IEC 60296 |
IEC 60422 |
||||
Voltage (HV) |
– |
<72.5 |
72.5 to 170 |
>170 |
||
Water content ppm (mg/kg) |
Max. 30 (bulk supply) Max. 40 (drums or IBC) |
Max. 20 |
Max. 10 |
Max. 10 |
||
Breakdown voltage (kV) |
Min. 30 |
Min. 55 |
Min. 60 |
Min. 60 |
VIMAP- |
|||||
Oil Characteristics |
Unit |
Before |
Pass No.1 |
Pass No. 2 |
Pass No. 3 |
Water Content |
ppm |
100 |
<20 |
<7 |
<5 |
Dielectric strength |
KV/cm (kV) |
80 (20) |
160 (40) |
240 (60) |
>280 (70) |
VIMAP- |
|||||
Type |
Flow |
Power consumption |
Dimensions |
Adsorbent capacity (without replacement)* |
Weight |
Lit/h |
kW |
mm |
Kg (oil) |
kg |
|
VIMAP- |
600 |
0,55 |
594x878x491 |
80000 |
110 |
* The average quantity of oil in kilograms which can be dehydrated without replacement of adsorbent cartridges, provided that there is no inlet of free water and tar into the device. Free water or tar draining from the bottom of tanks or transformers required. Replacement of cartridge with saturated adsorbent is done simply by means of quick release couplings. Device manual contains everything you need for easy operation and maintenance ** Other sizes available on request. |